One of the significant concerns in the MTDC systems is that voltage source converters (VSCs) do not hit their limits in the post-contingency conditions. Converters outage, DC line disconnection, and changeable output power of wind farms are the most common threats in these systems. Therefore, their destructive impact on neighboring AC systems should be minimized as much as possible. The fixed droop control is a better choice than others to deal with this, although it also has some limitations. Accordingly, a novel centralized droop-based control strategy considering N-1 contingency is proposed in this paper. It prevents converters from exceeding their limits while causes optimal power sharing and minimum DC link voltage deviation immediately, without secondary control layer. It also utilizes maximum wind power without curtailment. These properties improve the performance of the MTDC system in post-contingency conditions. The effectiveness of the proposed control method is validated by simulation of a 4-terminal VSC-MTDC system in MATLAB/Simulink R2016a.